Fluke T6-1000 Electrical Tester

  • FieldSense Technology: Allows for non-contact voltage and current measurement.
  • Simultaneous Voltage and Current Display: View both readings at once.
  • True-RMS Measurement: Ensures accurate measurements on complex waveforms.
  • Wide Jaw Opening: Accommodates large conductors.
  • Rugged and Durable: Built to withstand harsh environments.
  • Ergonomic Design: Comfortable to use.

Description

The Fluke T6-1000 is a revolutionary electrical tester that allows you to measure voltage and current without direct contact with live conductors. This innovative tool utilizes FieldSense technology to detect electrical fields, providing a safer and more efficient way to troubleshoot electrical systems.

Key Features:

  • FieldSense Technology: Enables non-contact voltage and current measurement.
  • Simultaneous Voltage and Current Display: View both readings at once for faster troubleshooting.
  • True-RMS Measurement: Ensures accurate measurements on complex waveforms.
  • Wide Jaw Opening: Accommodates large wires up to AWG 4/0 (120 mm²).
  • Rugged and Durable: Built to withstand harsh environments.
  • Ergonomic Design: Comfortable to use.

The Fluke T6-1000 is ideal for electrical professionals working in various industries, including residential, commercial, and industrial settings. Its compact design and easy-to-use interface make it a valuable tool for anyone who needs to measure voltage and current quickly and safely.

Additional information

Brand

Fluke

Specifications: Fluke T6-1000 Electrical Tester

Measurement Specifications
Function Requires test leads Range Resolution Accuracy[1]
FieldSense
ac voltage true-rms
No 1000 V 1 V ± (3 % + 3 counts) 45 Hz – 66 Hz[2][3]
FieldSense
ac current true-rms
No 200.0 A 0.1 A ± (3% + 3 counts) 45 Hz – 66 Hz
FieldSense
frequency (Hz)
No 45 Hz – 66 Hz 1 Hz ± (1% + 2 counts)[3]
Volts ac true-rms Yes 1000 V 1 V ± (1.5% + 2 counts) 45 Hz – 66 Hz
Volts dc Yes 1000 V 1 V ± (1% + 2 counts)
Resistance Yes 2000 Ω 1 Ω ± (1% + 2 counts)
Yes 20.00 kΩ 0.01 kΩ
Yes 100.0 kΩ 0.1 kΩ
Safety 1000 V CAT III
600 V CAT IV
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.
Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

 

General Specifications
Calibration 1-year calibration cycle
Dimensions 61.1 x 259.3 x 43.8 mm
Jaw opening 17.8 mm
Weight 0.35 kg (0.78 lb)
Temperature Operating -10 °C to +50 °C (14 °F to 122 °F)
Storage -30 °C to +60 °C (-22 °F to +140 °F)
Altitude Operating 2,000 m (6,562 feet)
Storage 10,000 m (32,808 feet)
Relative Humidity 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient 0.1 x (specified accuracy) / °C for <18°C or >28 °C
0.1 x (specified accuracy) / °C for <18°C or >28 °C
Safety IEC/EN 61010-1: Pollution Degree 2
Electromagnetic Environment IEC/EN 61326-1: Portable

 

Models: Fluke T6-1000 Electrical Tester
Includes:

  • Attached test leads with removable 4 mm probe caps
  • User documentation

Related Products