Fluke T6-600 Electrical Tester

Fluke T6-600 Electrical Tester

5 reasons the T6 belongs in your toolbelt

  • Be safer: Measure voltage to 600 V ac through the open fork, without test leads.
  • Be faster: No need to open covers or remove wire nuts.
  • Be more efficient: Simultaneously measure voltage and current.
  • Be everywhere: 17.8 mm open fork is widest in the industry; measure up to 200 A on 4/0 wires (120 mm2).
  • Go beyond simple detection. Actually measure ac voltage and current values without test leads.

 

More information contact below :

GET QUOTE021-4585-06180811-1519-949

Description

Fluke T6-600 Electrical Tester

Measure voltage … without test leads

We know working in electrical boxes jammed with wires can be challenging when you’re trying to find a safe metallic contact point. Now, with Fluke’s T6-600 or T6-1000 with integrated FieldSense technology, you can quickly and easily take measurements by sliding the open fork over a conductor to see the voltage level without the need for test leads.*

Why use the T6 Electrical Tester?

Electricians often work in boxes jammed with wires, where finding a safe metallic contact point can be a challenge. With the T6-600 or T6-1000 you take measurements by sliding a single wire into the open fork.

How FieldSense Works

FieldSense technology is truly a breakthrough in how voltage is measured. While other open fork testers detect a magnetic field to show ac current, FieldSense technology detects an electrical field. This field interacts with a reference signal created by the T6 tester, creating a voltage value on the tester’s display.

Who needs a T6 tester?

Commercial and light industrial electricians can use T6 Electrical Testers for most everyday measurements. These devices easily fit in your pocket, making them easy to access on the front-line for electricians of all industries.

* Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.

Specifications: Fluke T6-600 Electrical Tester

Measurement Specifications
FunctionRequires test leadsRangeResolutionAccuracy[1]
FieldSense
ac voltage true-rms
No600 V1 V±(3% + 3 counts) 45 Hz – 66 Hz[2] [3]
FieldSense
ac current true-rms
No200.0 A0.1 A±(3% + 3 counts) 45 Hz – 66 Hz
FieldSense
frequency (Hz)
No1 Hz±(1% + 2 counts)[3]
Volts ac true-rmsYes600 V1 V±(1.5% + 2 counts) 45 Hz – 66 Hz
Volts dcYes600 V1 V±(1% + 2 counts)
ResistanceYes2000 Ω1 Ω±(1% + 2 counts)
Safety600 V CAT III
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.

Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.

Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

General Specifications
Calibration1-year calibration cycle
Dimensions61.1 x 259.3 x 43.8 mm
Jaw opening17.8 mm
Weight0.35 kg (0.78 lb)
TemperatureOperating-10 °C to +50 °C (14 °F to 122 °F)
Storage-30 °C to +60 °C (-22 °F to +140 °F)
AltitudeOperating2,000 m (6,562 feet)
Storage10,000 m (32,808 feet)
Relative Humidity0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)
SafetyIEC/EN 61010-1: Pollution Degree 2
Electromagnetic EnvironmentIEC/EN 61326-1: Portable

Models: Fluke T6-600 Electrical Tester