Fluke 5322A Electrical Safety Tester Calibrator

  • Calibrates a wide range of equipment from Hipot testers to portable appliance testers.
  • Many functions in one instrument. Variable high voltage resistance outputs, Active Loop Compensation, a 600 V source, 4-wire low resistance sources, and optional high voltage load resistors.
  • Simulate RCD, display Ripple coefficient and THD measurements, with multiple models available.
  • Automate with MET/CAL software for improved consistency.

Description

The Fluke 5322A is a versatile and powerful calibration tool designed to simplify and streamline the calibration process for a wide range of electrical safety testers. Here’s an overview:

Key Features & Capabilities:

Multifunctionality:

  • Calibrates a wide range of equipment from Hipot testers to portable appliance testers.
  • Many functions in one instrument. Variable high voltage resistance outputs, Active Loop Compensation, a 600 V source, 4-wire low resistance sources, and optional high voltage load resistors.
  • Simulate RCD, display Ripple coefficient and THD measurements, with multiple models available.
  • Automate with MET/CAL software for improved consistency.
  • Hipot Testing: Calibrates AC and DC hipot testers with high accuracy.
  • Insulation Resistance Testing: Simulates various resistance values for calibrating insulation testers (megohmeters).
  • Loop Impedance & Ground Bond Testing: Provides precise resistance sources for calibrating loop impedance testers and ground bond testers.
  • RCD Testing: Simulates residual current devices (RCDs) for calibration.
  • High Accuracy: Ensures accurate and reliable calibration results for your electrical safety equipment.

Benefits:

  • Improved Efficiency: Streamlines calibration processes, saving time and resources.
  • Enhanced Accuracy: Ensures accurate and reliable calibration results, leading to more accurate and safer electrical safety testing.
  • Reduced Costs: Can help reduce the overall cost of ownership by minimizing downtime and improving equipment performance.
  • Increased Productivity: Enables faster turnaround times for calibrations, improving overall productivity.

The Fluke 5322A is a valuable asset for calibration laboratories, electrical safety professionals, and anyone involved in maintaining and calibrating electrical safety equipment. Its comprehensive capabilities, high accuracy, and user-friendly interface make it a reliable and efficient solution for ensuring the accuracy and reliability of critical safety equipment.

Additional information

Brand

Fluke Calibration

Specifications: 5322A Electrical Safety Tester Calibrator

Complete 5322A specifications

General specifications
Specifications confidence levell 99 %
Specifications interval 1 year
Power line 115/230 V ac (50/60 Hz) +10 % / -14 %, with the maximum voltage difference between neutral and protective earth not exceeding 15 V. Operation with power line between -10 % and -14 % has limitations in burden current for voltage outputs. See AC/DC Voltage Calibrator (VLC option) below.
Power consumption 1250 VA maximum
Fuse protection AC mains input: 2 A, 250 V for 230 V, time delay (T2L250 V – 5 mm x 20 mm) 4 A, 250 V for 115 V, time delay (T4L250 V – 5 mm x 20 mm)
RCD input: 3.15 A, 250 V, fast (F3.15H250 V – 5 mm x 20 mm)
Meter amps (A) input: 20 A, 500 V, time delay (F20H500 V – 6.3 mm x 32 mm)
Loop/Line impedance input: 4 A, 500 V, time delay (T4H500 V – 6.3 mm x 32 mm)
Leakage current input: 100 mA, 250 V, fast (F100 mL250 V – 5 mm x 20 mm)
Environment
Warm-up time 15 minutes
Temperature performance Operating temperature: 18 °C to 28 °C
Calibration temperature (tcal): 23 °C
Temperature coefficient for temperatures outside of tcal ± 5 °C is 0.1 / °C of the specification, for temperatures between 5 °C to 40 °C.
Storage temperature : -10 °C to 50 °C
Storage recovery time: Typically <24 hours at operating temperature
Relative humidity (operating) <80 % to 28 °C (resistance outputs >10 GΩ specified for <70 % to 28 °C)
Relative humidity (storage) 90 % non-condensing 0 °C to 50 °C
Altitude Operating: 2000 m (6561 ft)
Storage: 12 200 m (40 000 ft)
Dimensions and weight
Dimensions 430 mm x 555 mm x 170 mm (16.9 in x 21.8 in x 6.7 in)
Weight 20 kg (44.1 lb)
Compliance
Safety Mains: IEC 61010-1: Overvoltage category II, pollution degree 2
Measurement: IEC 61010-2-030: 5000 V (not category rated)
Electromagnetic compatibility (EMC)
International:

  • IEC 61326-1: Basic electromagnetic environment
  • CISPR 11: Group 1, Class A
    • Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
    • Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object.
Korea (KCC):

  • Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
USA (FCC):

  • 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Electrical specifications
Low resistance source
Range 100 mΩ to 10 kΩ + 10 mΩ single value selection, dc and line frequency (50/60 Hz)
1.5 kV high resistance source (DC only)
Range 10 kΩ to 10 GΩ + 100 GΩ single value selection
5.5 kV high resistance source (DC only) (5322A with /5 option)
Range 10 kΩ to 100 GΩ
Test voltage measurement
Range 0 V dc to 5500 V dc
Ground bond resistance source
Resistance mode
Range 1 mΩ to 1700 Ω, dc and line frequency (50/60 Hz)
Line/loop impedance source
Range 25 mΩ to 1700 Ω
Correction manual/scan mode
Residual impedance range 0 Ω to 10 Ω
Resolution 1 mΩ
Correction COMP mode (active loop compensation) (5322AVLC Option)
Maximum compensated impedance 0 Ω to 2 Ω
Leakage current source
Range 0.1 to 30 mA
Test voltage Passive mode: 60 V ac to 250 V ac rms
Differential mode: 60 V ac to 250 V ac rms
Substitute mode:10 V ac to 250 V ac rms
Active mode (5322A/VLC only)[1]: 50 V ac to 100 V ac rms
Uncertainty Passive mode: ± (0.3% setting + 2 μA)
Differential mode: ± (0.3% setting + 2 μA)
Test uncertainty can be influenced by power line voltage instability
Substitute mode: ± (0.3% setting + 2 μA)
Active mode (5322A/VLC only)[1]: ± (0.3% setting + 1 μA)
[1] The Active Mode outputs are synchronized with the ac mains frequency to suppress interference between the calibrator and external noise sources.
Human body simulation (for substitute leakage currently only Resistance range: 0 Ω to 10 000 Ω
Resolution: 1 Ω
RCD (residual current device) (for installation testers)
Trip current range 0.5 X I and 1 X I Mode: 5 to 30 mA in 1 mA steps
1.4 X I and 2 X I Mode: 14 to 60 mA in 1 mA steps
5 X I Mode: 50 to 150 mA in 1 mA steps
Trip current measurement resolution 1 μA below 30 mA
10 μA in range from 30 mA to 150 mA
100 μA in range from 300 mA to 3 A
Trip current measurement uncertainty
Trip current ± 1 % of nominal current (I) setting
Trip time range 10 to 5000 ms
Trip time uncertainty (0.02 % setting + 0.25 ms)
Touch/line voltage Touch voltage range: 50 V
Touch voltage setting: in discrete points depending on setup trip current value
Touch series resistance: 0.02 Ω, 0.05 Ω, 0.10 Ω, 0.35 Ω, 0.50 Ω, 0.96 Ω, 1.7 Ω, 4.7 Ω, 9 Ω, 17 Ω, 47 Ω, 90 Ω, 170 Ω, 470 Ω, 900 Ω, 1700 Ω
Line voltage range: 250 V
Line voltage uncertainty: ± (5 % reading + 3 V)
User selectable nominal line voltage: 100 V/115 V/120 V/220 V/230 V/240 V/250 V or real
Post-trip delayed power restore mode: user selectable
RCD (Residual current device (for PATs)
Trip current range 0.5 X I to 5 X I Mode: 5 to 150 mA in 1 mA steps
Trip current measurement resolution 1 μA
Trip current measurement uncertainty Trip current: ± 1 % of nominal current (I) setting
Trip time range 10 to 5000 ms
Trip time uncertainty (0.02 % setting + 0.25 ms)
Line voltage Reconnection delay: 2.5 s
AC/DC voltage calibrator (5322A with VLC Option)
Range 0.03 V to 600 V, ac or dc (.5 – 1%)
Internal ranges AC mode: 0.3 V to 600 V
DC mode: 0.3 V to 600 V
Multimeter 
Maximum withstand voltage HV terminal to COM terminal: 5000 V rms
V terminal to COM terminal:  1100 V rms
COM terminal to Protective Earth: 2200 V pk
AC/DC voltage range V (1100 V) Input:  0 V dc to ±1100 V dc 10 mV to 1100 V ac rms
HV (5000 V) Input: 0 Vdc to ±5000 Vdc 5 V to 5000 V ac rms
AC/DC current
Range 0 A to 20 A continuous, 20 A to 30 A for up to 5 minutes, ac rms or dc
AC power
Range 0 kVA ac to 33 kVA ac
Type Apparent, active, reactive
Phase indication Phase angle (φ), Power Factor (PF)
Phase uncertainty (dφ) ± 0.1 °
DC power
Range 0 to 33 kVA dc
Hipot ac voltage distortion measurement
Frequency range 45 Hz to 65 Hz
Number of harmonics 25
Hipot dc voltage ripple coefficient measurement
Voltage range 100 V dc to 5000 V dc
Ripple coefficient range 10 %
Flash test voltage measurement (using flash LC or flash V mode)
Class I Voltage range 2000 V ac rms
Uncertainty ± (0.3 % of reading + 6 V)
Class II Voltage range 3000 V ac rms
Uncertainty ± (1 % of reading value + 6 V)
Flash leakage current measurement (using flash LC mode)
Range 0 mA ac rms or dc to 300 mA ac rms or dc
Resolution 4.5 digits

 

Related Products