Testo 300 Kit 2 Flue Gas Analyzer O2 CO H2 up to 8,000 ppm
- Fast and easy to operate: intuitive measurement menus and fast-response Smart-Touch display
- Including O2, CO H2-compensated sensor up to 8,000 ppm
- Large 5-inch HD display – see all the system’s measuring values at a glance
- In the kit: testo 300 flue gas analyzer, including O2 and CO H2-compensated sensor up to 8,000 ppm, mains unit, basic flue gas probe, spare dirt filters, EasyHeat software, instrument bag
- Description
- Additional information
- Specifications
Description
The Testo 300 Kit 2 is a flue gas analyzer designed for comprehensive combustion analysis of heating systems.
Key Features:
- Fast and easy to operate: intuitive measurement menus and fast-response Smart-Touch display
- Including O2, CO H2-compensated sensor up to 8,000 ppm
- Large 5-inch HD display – see all the system’s measuring values at a glance
- In the kit: testo 300 flue gas analyzer, including O2 and CO H2-compensated sensor up to 8,000 ppm, mains unit, basic flue gas probe, spare dirt filters, EasyHeat software, instrument bag
- TÜV-tested: Ensures compliance with relevant safety and performance standards.
- Enhanced measurement capabilities: Includes O2 and CO sensors for accurate combustion analysis, often with the addition of NO sensors for more in-depth assessments.
- User-friendly interface: Features an intuitive touch display and easy-to-navigate menus.
- Compact and portable: Designed for convenient transport and on-site use.
- Includes: Flue gas analyzer, basic flue gas probe, instrument case, and essential accessories.
Applications:
- Heating system installation and maintenance: Assess combustion efficiency and identify potential issues.
- Troubleshooting: Diagnose problems with heating systems based on flue gas analysis.
- Compliance checks: Verify that systems meet environmental regulations and safety standards.
- Advanced analysis: Conduct more in-depth investigations due to the inclusion of NO sensors (specific to models with NO capabilities).
With Testo 300 Kit 2, you will be equipped for the most important measurements involving heating systems: the TÜV-tested testo 300 flue gas analyzer is supplied with O2 CO H2 sensor up to 8,000 ppm, basic flue gas probe, instrument case and practical accessories.
Additional information
Brand | Testo |
---|
Measurement parameter | Measuring range | Accuracy (±1 digit) | Resolution |
O2 measurement | 0 to 21 vol. % | ±0.2 vol. % | 0.1 vol. % |
CO measurement
(without H2 compensation) |
0 to 4,000 ppm | ±20 ppm (0 to 400 ppm)
±5 % of m.v. (401 to 2,000 ppm) ±10 % of m.v. (2,001 to 4,000 ppm) |
1 ppm |
CO measurement
(with H2 compensation) |
0 to 8,000 ppm | ±10 ppm or ± 10 % of m.v. (0 to 200 ppm)
±20 ppm or ± 5 % of m.v. (201 to 2,000 ppm) ±10 % of m.v. (2,001 to 8,000 ppm) |
1 ppm |
CO measurement
(without H2 compensation with dilution) |
0 to 15,000 ppm | ±200 ppm or ± 20 % of m.v. | 1 ppm |
CO measurement
(with H2 compensation and dilution) |
0 to 30,000 ppm | ±100 ppm or ± 10 % of m.v. | 1 ppm |
COlow measurement
(with H2 compensation) |
0 to 500 ppm | ±2 ppm (0 to 40 ppm)
±5 % of m.v. (remaining meas. range) |
0.1 ppm |
NO measurement | 0 to 3,000 ppm | ±5 ppm (0 to 100 ppm)
±5 % of m.v. (101 to 2,000 ppm) ±10 % of m.v. (2,001 to 3,000 ppm) |
1 ppm |
NOlow measurement | 0 to 300 ppm | ±2 ppm (0 to 39.9 ppm)
±5 % of m.v. (40 to 300 ppm) |
0.1 ppm |
Efficiency testing (Eta) | 0 to 120 % | 0.1 % | |
Flue gas loss | 0 to 99.9 % | 0.1 % | |
CO2 determination
(digital calculation from O2) |
Display range
0 to CO2 max. |
±0.2 vol. % | 0.1 vol. % |
Draught measurement | -9.99 to +40 hPa | ±0.005 hPa (0 to 0.1 hPa)
±0.02 hPa (0.1 to +3.00 hPa) ±1.5 % of m.v. (+3.01 to +40 hPa) |
0.001 hPa (0 to 0.1 hPa)
0.01 hPa (remaining meas. range) |
4 Pa measurement
(for instruments with dilution) |
-50 to +50 Pa | ±0.3 Pa (< 10 Pa)
±3 % of m.v. (remaining meas. range) |
0.1 Pa |
Pressure measurement | -100 to +200 hPa | ±0.5 hPa (0 to +50.0 hPa)
±1 % of m.v. (+50.1 to +100.0 hPa) ±1.5 % of m.v. (+100.1 to +200 hPa) |
0.01 hPa |
Temperature (instrument) | -40 to +1,200 °C | ±0.5 °C (0.0 to +100.0 °C)
±0.5 % of m.v. (remaining meas. range) |
0.1 °C (-40 to +999.9 °C)
1 °C (remaining meas. range) |
Ambient CO measurement
(internal/flue gas probe) |
0 to 2,000 ppm | ±10 ppm (0 to 100 ppm)
±10 % of m.v. (101 to 2,000 ppm) |
1 ppm |
Ambient CO measurement
(external with CO probe) |
0 to 500 ppm | ±3 ppm (0 to 29 ppm)
±10 % of m.v. (30 to 500 ppm) |
1 ppm |