Gossen METRACLIP 88 Clamp Multimeter

  • Clamp opening: 60 mm
  • Current:
    • AC 99,99 / 999,9 / 2000 A rms bei 10 Hz – 1 kHz
    • DC ±99,99 / ±999,9 / ±3000 A dc
    • AC+DC 99,99 / 999,9 / 2000 A rms
    • 99,99 / 999,9 / 3000 A peak
  • Inrush current: 20 ..2000 A rms / 3000 A peak
  • Voltage:
    • AC 99,99 / 999,9 V rms bei 10 Hz – 3 kHz
    • DC ±99,99 / ±999,9 V dc
    • AC+DC 99,99 / 999,9 V rms
    • 99,99 / 999,9 / 1400 V peak
  • Frequency:
    • f (Uac) 5,0 Hz ..19,99 kHz
    • f (Iac) 5,0 Hz ..999,9 Hz
  • Power:
    • Active power: 9999 W / 99,99 / 999,9 / 3000 kW
    • Apparent power: 9999 VA / 99,99 / 999,9 / 3000 kVA
    • Reactive power: 9999 var / 99,99 / 999,9 / 3000 kvar
    • PF -1,00 ..+1,00
    • DPF 0,00 ..1,00
  • Distortion:
    • Ripple 0,1 ..1000 %
    • CF 1,00 ..10,00
    • THDr / THDf 0,0 ..100 % / 0,0 ..1000 %
Category:

Description

The METRACLIP 88 is a high-performance clamp meter from Gossen Metrawatt specifically designed for measuring high currents and power in industrial environments.

Key Features:

  • Electrical safety per IEC 61010
  • TRMS measurement
  • Current measurement (AC and DC)
  • Voltage measurement (AC and DC)
  • Power measurement (W, VA, var and PF)
  • THD measurement
  • Starting and overcurrent measurement (true inrush)
  • Frequency measurement
  • Automatic measuring range selection
  • Relative and differential measurements
  • Display value storage (Data Hold)
  • Data logging (min., max., peak)
  • Continuity test, acoustic signal
  • Resistance measurement
  • Diode test
  • Phase sequence display
  • Phase sequence
  • LCD / digits backlit in blue10,000
  • Auto power-off
  • Test report incl.
  • High Current Measurement: Measures high AC/DC currents with a wide measurement range.
  • Large Clamp Opening: Accommodates large conductors, making it suitable for measuring current in thick cables or busbars.
  • Power Measurements: Measures active, apparent, and reactive power.
  • True RMS Measurement: Ensures accurate readings even with non-sinusoidal waveforms.
  • Contactless Current Measurement: Enables safe and efficient current measurement without touching the conductor.
  • Rugged Construction: Built to withstand the demands of industrial environments.

Applications:

  • Industrial Maintenance: Monitoring current flow in motors, transformers, and other high-power industrial equipment.
  • Power Distribution: Measuring current and power in power lines and substations.
  • Electrical Installation: Troubleshooting high-current circuits and verifying proper installation.

In essence, the METRACLIP 88 is a robust and reliable tool for professionals who need to measure high currents and power accurately and safely in demanding industrial environments.

Additional information

Brand

Gossen Metrawatt

Characteristic Values

METRACLIP 86 METRACLIP 85 METRACLIP 88 METRACLIP 87
Item number M312K M312J M312M M312L
Reactive power AC 1Watt – 600000Watt 1Watt – 2000000Watt 1Watt – 1000000Watt
Continuity test x x x x
THDr 0.001 – 1 0.0001 – 1 0.0001 – 1
Reactive power AC+DC 1Watt – 900000Watt 1Watt – 3000000Watt 1Watt – 1500000Watt
Frequency measuring range for AC currents 1Hertz – 3000Hertz 0.1Hertz – 3000Hertz 0.1Hertz – 1000Hertz 0.1Hertz – 2000Hertz
Frequency measuring range for AC voltages 1Hertz – 20000Hertz 0.1Hertz – 20000Hertz 0.1Hertz – 20000Hertz 0.1Hertz – 20000Hertz
Max. voltage measuring circuit category 600Volt 600Volt 1000Volt 1000Volt
Diode test x x x
Voltage measuring range AC 0.1Volt – 1000Volt 0.01Volt – 1000Volt 0.01Volt – 1000Volt 0.01Volt – 1000Volt
Phase sequence determination x x
Apparent power AC 1Voltampere – 600000Voltampere 1Voltampere – 2000000Voltampere 1Voltampere – 1000000Voltampere
THDf 0.001 – 10 0.0001 – 10 0.0001 – 10
AC measuring method TRMS TRMS TRMS TRMS
Intrinsic uncertainty of the measured value in % 0.4Percentage 0.4Percentage 1Percentage 1Percentage
Active power DC 1Watt – 900000Watt 1Watt – 3000000Watt 1Watt – 1500000Watt
Power factor PF 0.01 – 1 0.01 – 1 0.01 – 1
Resistance measurement range 0.1Ohm – 60000Ohm 0.1Ohm – 60000Ohm 0.1Ohm – 1000Ohm 0.1Ohm – 100000Ohm
Measured value memory HOLD
MAX
MIN
PEAK
HOLD
MIN
MAX
HOLD
MAX
MIN
PEAK
HOLD
MAX
MIN
PEAK
Active power AC+DC 1Watt – 900000Watt 1Watt – 3000000Watt 1Watt – 1500000Watt
Active power AC 1Watt – 600000Watt 1Watt – 2000000Watt 1Watt – 1000000Watt
Apparent power AC+DC 1Voltampere – 900000Voltampere 1Voltampere – 3000000Voltampere 1Voltampere – 1500000Voltampere
Voltage measuring range DC 0.1Volt – 1000Volt 0.01Volt – 1000Volt 0.01Volt – 1000Volt 0.01Volt – 1000Volt
Indication Digital Digital Digital Digital
Analogue bar graph display
Measuring range selection Automatic Automatic Automatic Automatic
Current measuring range, DC 0.01 – 900 0.01 – 900 1 – 3000 0.01 – 1500
Current measuring range, AC 1 – 600 0.01 – 600 1 – 2000 0.01 – 1500
Type of current AC/DC AC/DC AC/DC AC/DC
True RMS measurement x x x x
Voltage measurement, AC x x x x
Voltage measurement, DC x x x x
Resistance measuring range x x x x
Power measuring x x x
Leakage current measuring x x x x
Harmonics measurement x x x
Measurement in cables with for- and back conductor x x x x
Jaw opening 34 34 60 48
Version as adapter to connect to multi meter
Interface x
Measuring circuit category CAT IV CAT IV CAT IV CAT IV
Adapter function AC
Frequency range alternating current 0Hertz – 1000Hertz 0Hertz – 2000Hertz
Temperature measuring range
Adapter function DC
Frequency range volt AC 0Hertz – 3000Hertz 0Hertz – 3000Hertz
Displacement factor DPF 0.01 – 1
Ripple 0.1 – 10
Crest factor CF 1 – 10
Voltage measuring range AC+DC 0.01Volt – 1000Volt
Current measurement range AC+DC 0.01Ampere – 1500Ampere

 