Gossen METRACLIP 86 Clamp Multimeter
- Clamp opening: 34 mm
- Current:
- AC 60,00 / 600,0 A rms bei 10 Hz – 3 kHz
- DC ±60,00 / ±600,0 / ±900 A dc
- AC+DC 60,00 / 600,0 A rms
- 60,00 / 600,0 / 900 A peak
- Inrush current:
- 6 ..600 A rms / 900 A peak
- Voltage:
- AC 60,00 / 600,0 / 1000 V rms bei 10 Hz – 3 kHz
- DC ±60,00 / ±600,0 / ±1000 V dc
- AC+DC 60,00 / 600,0 / 1000 V rms
- 60,00 / 600,0 / 1400 V peak
- Frequency:
- f (Uac) 5,0 Hz ..19,99 kHz
- f (Iac) 5,0 Hz ..2999 Hz
- Power:
- Active power: 5999 W / 59,99 / 599,9 / 900 kW
- Apparent power: 5999 VA / 59,99 / 599,9 / 900 kVA
- Reactive power: 5999 var / 59,99 / 599,9 / 900 kvar
- PF -1,00 ..+1,00
- Distortion: THDr / THDf 0,0 ..100% / 0,0 ..1000%
- Description
- Additional information
- Specifications
Description
The METRACLIP 86 is a high-performance clamp meter from Gossen Metrawatt designed for comprehensive electrical measurements in various applications.
Key Features:
- Electrical safety per IEC 61010
- TRMS measurement
- Current measurement (AC and DC)
- Voltage measurement (AC and DC)
- Power measurement (W, VA, var and PF)
- THD measurement
- Starting and overcurrent measurement (true inrush)
- Frequency measurement
- Automatic measuring range selection
- Relative and differential measurements
- Display value storage (Data Hold)
- Data logging (min., max., peak)
- Continuity test, acoustic signal
- Resistance measurement
- Diode test
- Phase sequence display
- Phase sequence
- LCD / digits backlit in blue 6,000
- Auto power-off
- Test report incl.
- Versatile Measurements: Measures AC/DC current, voltage, resistance, frequency, power (active, apparent, reactive), and more.
- High Accuracy: Provides precise measurements with high accuracy.
- True RMS Measurement: Ensures accurate readings even with non-sinusoidal waveforms.
- Contactless Current Measurement: Enables safe and efficient current measurement without touching the conductor.
- Data Logging: Some models may offer data logging capabilities for recording measurements over time.
- Advanced Features: May include features like harmonic analysis, inrush current measurement, and motor testing.
Applications:
- Industrial Maintenance: Troubleshooting electrical problems in industrial equipment, monitoring motor currents, and performing predictive maintenance.
- Electrical Installation: Checking for voltage presence, verifying wiring, and troubleshooting electrical circuits.
- Energy Audits: Assessing energy consumption and identifying areas for energy efficiency improvement.
- Research and Development: Used in various research and development projects involving electrical systems.
In essence, the METRACLIP 86 is a powerful and versatile tool for electricians, technicians, and engineers who require a comprehensive and accurate solution for a wide range of electrical measurements.
Additional information
Brand | Gossen Metrawatt |
---|
Characteristic Values
METRACLIP 86 | METRACLIP 85 | METRACLIP 88 | METRACLIP 87 | |
Item number | M312K | M312J | M312M | M312L |
Reactive power AC | 1Watt – 600000Watt | 1Watt – 2000000Watt | 1Watt – 1000000Watt | |
Continuity test | x | x | x | x |
THDr | 0.001 – 1 | 0.0001 – 1 | 0.0001 – 1 | |
Reactive power AC+DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Frequency measuring range for AC currents | 1Hertz – 3000Hertz | 0.1Hertz – 3000Hertz | 0.1Hertz – 1000Hertz | 0.1Hertz – 2000Hertz |
Frequency measuring range for AC voltages | 1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz |
Max. voltage measuring circuit category | 600Volt | 600Volt | 1000Volt | 1000Volt |
Diode test | x | x | x | |
Voltage measuring range AC | 0.1Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt |
Phase sequence determination | x | x | ||
Apparent power AC | 1Voltampere – 600000Voltampere | 1Voltampere – 2000000Voltampere | 1Voltampere – 1000000Voltampere | |
THDf | 0.001 – 10 | 0.0001 – 10 | 0.0001 – 10 | |
AC measuring method | TRMS | TRMS | TRMS | TRMS |
Intrinsic uncertainty of the measured value in % | 0.4Percentage | 0.4Percentage | 1Percentage | 1Percentage |
Active power DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Power factor PF | 0.01 – 1 | 0.01 – 1 | 0.01 – 1 | |
Resistance measurement range | 0.1Ohm – 60000Ohm | 0.1Ohm – 60000Ohm | 0.1Ohm – 1000Ohm | 0.1Ohm – 100000Ohm |
Measured value memory | HOLD MAX MIN PEAK |
HOLD MIN MAX |
HOLD MAX MIN PEAK |
HOLD MAX MIN PEAK |
Active power AC+DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Active power AC | 1Watt – 600000Watt | 1Watt – 2000000Watt | 1Watt – 1000000Watt | |
Apparent power AC+DC | 1Voltampere – 900000Voltampere | 1Voltampere – 3000000Voltampere | 1Voltampere – 1500000Voltampere | |
Voltage measuring range DC | 0.1Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt |
Indication | Digital | Digital | Digital | Digital |
Analogue bar graph display | ||||
Measuring range selection | Automatic | Automatic | Automatic | Automatic |
Current measuring range, DC | 0.01 – 900 | 0.01 – 900 | 1 – 3000 | 0.01 – 1500 |
Current measuring range, AC | 1 – 600 | 0.01 – 600 | 1 – 2000 | 0.01 – 1500 |
Type of current | AC/DC | AC/DC | AC/DC | AC/DC |
True RMS measurement | x | x | x | x |
Voltage measurement, AC | x | x | x | x |
Voltage measurement, DC | x | x | x | x |
Resistance measuring range | x | x | x | x |
Power measuring | x | x | x | |
Leakage current measuring | x | x | x | x |
Harmonics measurement | x | x | x | |
Measurement in cables with for- and back conductor | x | x | x | x |
Jaw opening | 34 | 34 | 60 | 48 |
Version as adapter to connect to multi meter | ||||
Interface | x | |||
Measuring circuit category | CAT IV | CAT IV | CAT IV | CAT IV |
Adapter function AC | ||||
Frequency range alternating current | 0Hertz – 1000Hertz | 0Hertz – 2000Hertz | ||
Temperature measuring range | ||||
Adapter function DC | ||||
Frequency range volt AC | 0Hertz – 3000Hertz | 0Hertz – 3000Hertz | ||
Displacement factor DPF | 0.01 – 1 | |||
Ripple | 0.1 – 10 | |||
Crest factor CF | 1 – 10 | |||
Voltage measuring range AC+DC | 0.01Volt – 1000Volt | |||
Current measurement range AC+DC | 0.01Ampere – 1500Ampere |