Fluke 1736 and 1738 Three-Phase Power Quality Loggers
- Voltage and current waveforms
- Power, power factor, and energy consumption
- Harmonics and interharmonics
- Description
- Additional information
- Specifications
Description
The Fluke 1736 and 1738 are robust and versatile three-phase power quality loggers designed to help you diagnose, quantify, and resolve power quality issues. These tools are essential for electrical engineers, technicians, and facility managers who strive for reliable and efficient electrical systems.
Key Features and Benefits:
- Comprehensive Power Quality Measurements: Both models provide a wide range of measurements, including:
- Voltage and current waveforms
- Power, power factor, and energy consumption
- Harmonics and interharmonics
- Unbalance, flicker, and rapid voltage changes
- Power quality disturbances and transients
- User-Friendly Interface: The intuitive, color touchscreen interface simplifies setup, data review, and analysis.
- Flexible Connectivity: With USB, Wi-Fi, and Bluetooth connectivity, you can seamlessly transfer data and monitor remotely.
- Powerful Analysis Software: The included Energy Analyze Plus software empowers you with in-depth analysis, detailed reporting, trend identification, and root cause analysis.
- Rugged and Reliable Design: Built to withstand harsh environments, these loggers are durable and reliable.
Model-Specific Capabilities:
- Fluke 1736: Ideal for basic power quality assessments and energy audits. It measures fundamental parameters like voltage, current, power, power factor, and energy consumption.
- Fluke 1738: Offers advanced power quality logging capabilities, including harmonic and interharmonic analysis, unbalance measurements, and flicker measurements. It’s perfect for more complex power quality investigations.
Additional information
| Brand | Fluke |
|---|
Specifications: Fluke 1736 and 1738 Three-Phase Power Quality Loggers
| Specifications | |||||
| Accuracy | |||||
| Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale) | ||
| Voltage | 1000 V | 0.1 V | ±(0.2% + 0.01%) | ||
| Current: Direct input | i17xx-flex 1500 12″ | 150 A | 0.1 A | ±(1% + 0.02%) | |
| 1500 A | 1 A | ±(1% + 0.02%) | |||
| i17xx-flex 3000 24″ | 300 A | 1 A | ±(1% + 0.03%) | ||
| 3000 A | 10 A | ±(1% + 0.03%) | |||
| i17xx-flex 6000 36″ | 600 A | 1 A | ±(1.5% + 0.03%) | ||
| 6000 A | 10 A | ±(1.5% + 0.03%) | |||
| i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
| 40 A | 10 mA | ±(0.7% + 0.02%) | |||
| Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%) | ||
| Auxillary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
| Voltage min/max | 1000 V | 0.1 V | ±(1% + 0.1%) | ||
| Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
| THD on voltage | 1000% | 0.1% | ±0.5 | ||
| THD on current | 1000% | 0.1% | ±0.5 | ||
| Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | ≥ 10 V: ±5% of reading | ||
| < 10 V: ±0.5V | |||||
| Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | ≥ 3% of current range: ±5% of reading | ||
| < 3% of current range: ±0.15% of range | |||||
| Unbalance | 100% | 0.1% | ±0.2 | ||
| Intrinsic Uncertainty ±(% of reading +% of range)¹ | |||||
| Parameter | Influence quantity | iFlex1500-12 | iFlex3000-24 | iFlex6000-36 | i40S-EL |
| 150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
| Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Active Energy Ea | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Apparent Energy Eap | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
| Reactive Energy Er | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
| Power Factor PF | – | ±0.025 | |||
| Displacement Power Factor | – | ±0.025 | |||
| DBF/cosϕ | – | ±0.025 | |||
| Additional uncertainty in% of range¹ | VP-N>250 V | 0.015% | 0.0225% | 0.0225% | 0.015% |
| ¹Range = 1000 V x Irange Reference conditions:
|
|||||
| Electrical Specifications | |
| Power Supply | |
| Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
| 100 V to 240 V using standard power cord (IEC 60320 C7) | |
| Power consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
| Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) |
| Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input |
| Mains power frequency | 50/60 Hz ±15% |
| Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-battery runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode |
| Charging time | < 6 hours |
| Data Acquisition | |
| Resolution | 16-bit synchronous sampling |
| Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
| Circuit types | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies) |
| Data storage | Internal flash memory (not user replaceable) |
| Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹ |
| ¹The number of possible logging sessions and logging period depends on user requirements. | |
| Basic Interval | |
| Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms |
| Demand Interval (Energy Meter Mode) | |
| Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Power Quality Measurements | |
| Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD |
| Averaging interval | 10 min |
| Individual harmonics | 2nd to 50th harmonic |
| Total harmonic distortion | Calculated on 50 harmonics |
| Events | Voltage: dips, swells, interruptions, current: inrush current |
| Triggered recordings | Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30) |
| Waveform of voltage and current (1738) | |
| Standards Compliance | |
| Harmonics | IEC 61000-4-7: Class 1 |
| IEEE 519 (short time harmonics) | |
| Power quality | IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device) |
| Power | IEEE 1459 |
| Power quality compliance | EN50160 (for measured parameters) |
| Interfaces | |
| USB-A | File transfer via USB flash drive, firmware updates Max. current: 120 mA |
| WiFi | File transfer and remote control via direct connection or WiFi infrastructure |
| Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option) |
| USB-mini | Data download device to PC |
| Voltage Inputs | |
| Number of inputs | 4 (3 phases and neutral) |
| Maximum input voltage | 1000 Vrms, CF 1.7 |
| Input impedance | 10 MΩ |
| Bandwidth (-3 dB) | 42.5 Hz – 3.5 kHz |
| Scaling | 1:1 and variable |
| Measurement category | 1000 V CAT III/600 V CAT IV |
| Current Inputs | |
| Number of inputs | 4, mode selected automatically for attached sensor |
| Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
| Rogowski coil input | 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
| Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12″ |
| 3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24″ | |
| 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36″ | |
| 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |
| Bandwidth (-3 dB) | 42.5 Hz – 3.5 kHz |
| Scaling | 1:1 and variable |
| Auxiliary Inputs | |
| Number of inputs | 2 |
| Input range | 0 to ±10 V dc, 1reading/s |
| Scale factor | Format: mx + b (gain and offset) user configurable |
| Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Connection | |
| Number of inputs | 2 |
| Supported modules | Fluke Connect® 3000 series |
| Acquisition | 1 reading/s |
| Environmental Specifications | |
| Operating temperature | -10 °C to +50 °C (14 °F to 122 °F) |
| Storage temperature | -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F) |
| Operating humidity | 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH |
| 30 °C to 40 °C (86 °F to 104 °F) max. 75% RH | |
| 40 °C to 50 °C (104 °F to 122 °F) max. 45% RH | |
| Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Storage altitude | 12,000m |
| Enclosure | IP50 in accordance with EN60529 |
| Vibration | MIL-T-28800E, Type 3, Class III, Style B |
| Safety | IEC 61010-1 |
| IEC Mains Input: Overvoltage Category II, Pollution Degree 2 | |
| Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 | |
| IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V | |
| Electromagnetic compatibility | EN 61326-1: Industrial CISPR 11: Group 1, Class A |
| Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |
| USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
| Temperature coefficient | 0.1 x accuracy specification/°C |
| General Specifications | |
| Color LCD display | 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel |
| Warranty | Instrument and power supply: Two-years (battery not included) |
| Accessories: one-year | |
| Calibration cycle: two-years | |
| Dimensions | Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) |
| Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) | |
| Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in) | |
| Weight | Instrument: 1.1 kg (2.5 lb) |
| Power supply: 400 g (0.9 lb) | |
| Tamper protection | Kensington lock slot |
| i17xx-flex 1500 12″ Flexible Current Probe Specifications | |
| Measuring range | 1 to 150 A ac/10 to 1500 A ac |
| Nondestructive current | 100 kA (50/60 Hz) |
| Intrinsic error at reference condition* | ±0.7% of reading |
| Accuracy 173x + iFlex | ±(1% of reading + 0.02% of range) |
| Temperature coefficient over operating temperature range | 0.05% of reading/°C 0.09% of reading/°F |
| Working voltage | 1000 V CAT III, 600 V CAT IV |
| Probe cable length | 305 mm (12 in) |
| Probe cable diameter | 7.5 mm (0.3 in) |
| Minimum bending radius | 38 mm (1.5 in) |
| Output cable length | 2 m (6.6 ft) |
| Weight | 115 g |
| Probe cable material | TPR |
| Coupling material | POM + ABS/PC |
| Output cable | TPR/PVC |
| Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) |
| Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) |
| Relative humidity, operating | 15% to 85% non-condensing |
| IP rating | IEC 60529:IP50 |
| Warranty | One-year |
* Reference condition:
|
|
Related Products
- Automatically capture and log voltage, current, power, power factor, energy and associated values
- 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
- Measure key power quality parameters
- Measure with premium accuracy rigorous IEC 61000-4-30 Class A Edition 3 standard
- Flexible and fully configurable thresholds and scale factors
- Uninterrupted power supply (40 minutes)
- Power quality statistics according to EN50160
- Three-phase power quality recorder fully compliant to IEC 61000-4-30 Class-A and consistent with compliance testing
- Uses GPS time synchronization to correlate data with events or datasets from other instruments with precision
- Flexible and fully configurable thresholds and scale factors
- 10 MHz, 6000 Vpk waveform capture
- Power quality statistics according to EN50160
- Flexible and fully configurable thresholds and scale factors
- Uninterrupted power supply (40 minutes)
- 10 MHz, 6000 Vpk waveform capture
- Automatically measure power and power quality parameters
- Easily view V/A/Hz, power, dips, swells, and harmonics data
- Capture high-speed transients up to 8 kV
- Features a simple user interface to ensure easy, intuitive operation
- Measures voltage, current, and power harmonics up to the 40th harmonic for complete analysis
- Six-phase power analyzer for developing frequency converters and lighting equipment
- Measures voltage, current, and power harmonics up to the 40th harmonic
- Measure voltage, current, active power, reactive power, apparent power, power factor and harmonics with associated values
- Get accurate, precise results with 0.1% measurement accuracy and a 500kHz bandwidth
- This product is discontinued or reclassified
- Single-phase, plug-in voltage quality recorder for detecting and recording power quality problems
- Records voltage trends, dropouts, and power quality to pinpoint the root cause
- Measuring category: 600 V CAT III / 300 V CAT IV
- Sampling rate: 18 kHz
- Acquisition of voltage dips and swells, overvoltage, asymmetry, flicker
- 3 voltage channels – direct measurements up to 600 V RMS, CAT III
- 4 current channels – 0.333 V RMS current inputs, compatible with various optional accessories (see accessories lists) and all 0.333 V RMS current transformers which comply with industry standards
- Measurement types: V, I, W (P), VA (S), VAR (Q), PF, demand measurement for various quantities, energy … and much more
- 4-voltage channels with wide measurement range: 0 … 1000 Vrms (CAT III / 1000 V);
- 4-current channels with support for automatic clamp recognition and “on instrument“ range selection;
- Sampling frequency on transients recording 49 kSamples/sec on 8 channels simultaneously;
- 4-voltage channels with wide measurement range;
- 4-current channels with support for automatic clamp recognition and “on instrument“ range selection;
- Sampling frequency on transients recording > 1 MSamples/sec, on 8 channels simultaneously;
- Voltage: TRMS, DC, fundamental, under, over, peak, crest factor (4-channel)
- Current: TRMS, DC, fundamental, peak, crest factor (4-channel)
- Support for different connections: 1W, 2W (split), 3W, open delta, 4W, INV-3W, INV-1W