Fluke 1663 Installation Multifunction Tester

Comprehensive Testing Capabilities:

  • Voltage and frequency measurement
  • Resistance measurement
  • Continuity testing
  • Earth resistance measurement
  • Loop impedance testing
  • RCD testing (including Type B RCDs)
  • Insulation resistance testing
  • Polarity testing
  • Phase rotation testing

Description

The Fluke 1663 Multifunction Installation Tester is a powerful tool designed to streamline and enhance the efficiency of electrical installations. This versatile device offers a comprehensive suite of testing capabilities, ensuring the safety and compliance of electrical systems in various settings.

Key Features:

Comprehensive Testing Capabilities: The 1663 covers a wide range of essential tests, including:

  • Voltage and frequency measurement
  • Resistance measurement
  • Continuity testing
  • Earth resistance measurement
  • Loop impedance testing
  • RCD testing (including sensitive Type B RCDs)
  • Insulation resistance testing
  • Polarity testing
  • Phase rotation testing

Applications:

  • Electrical Installations: Verifying the safety and compliance of new installations.
  • Periodic Inspections: Conducting routine inspections to identify potential hazards and ensure ongoing safety.
  • Fault Finding: Diagnosing electrical faults and troubleshooting issues.
  • Maintenance and Repair: Supporting maintenance and repair activities.

Benefits:

  • Enhanced Safety: By ensuring the correct functioning of electrical systems, the 1663 helps prevent accidents and electrical shocks.
  • Increased Efficiency: Automated tests and streamlined workflows improve productivity.
  • Accurate and Reliable Results: Precise measurements and advanced features ensure accurate and reliable test results.
  • Compliance with Standards: The 1663 helps users comply with relevant electrical safety standards and regulations.

Overall, the Fluke 1663 is a valuable tool for electrical professionals, providing a comprehensive solution for testing, troubleshooting, and maintaining electrical installations. Its advanced features, user-friendly interface, and robust design make it an essential tool for ensuring safety and efficiency in the electrical industry.

Additional information

Brand

Fluke

Specifications: Fluke 1663 Installation Multifunction Tester

Specifications: Fluke 1663 and 1664 FC Installation Multifunction Testers

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Test voltages 50-100-250-500-1000 V
Accuracy of test voltage (at rated test current) +10%, -0%
Test voltage 50 V
100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Resolution 0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type AC¹
G²,S³
Model 1663 A4, AC¹, G²,S³
Model 1664 FC A, AC, B5, S
Notes ¹Responds to AC
²General, no delay
³Time delay
⁴Responds to pulsed signal
⁵Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
VAR Mode Type B – 6, 60, 200 mA
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
EV / RDC-DD 6 mA – 10s
60 mA – 0.3s
200 mA – 0.1s
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA).
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
<2 mA to 6 mA smooth DC³
Step size 10% of IΔN²
Linear rising within 30 s
Dwell time RCD Type G 300 ms/step
RCD Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
²5% for Type B
³For RCD type A-EV/RDC-DD acc. to IEC 62955
Earth Resistance Test (RE)
Range 200 Ω / 2000 Ω
Resolution 0.1 Ω / 1Ω
Frequency 128 Hz
Output Voltage 25 V
Phase Sequence Indication
Icon      Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 Kg
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 and EN61557-10

 

Models: Fluke 1663 Installation Multifunction Tester
Includes:

  • 6x AA (IEC LR6) cell batteries
  • C1600 hard carrying case
  • Zero adapter
  • Heavy duty mains cord
  • STD standard test lead set
  • Padded carrying and waist strap
  • Quick reference guide
  • TP165X remote control probe and lead