Fluke 1535 and 1537 Insulation Resistance Tester Megohmmeters

  • User-selectable test voltages: Choose from 250 V, 500 V, 1000 V, and 2500 V to suit various testing needs.
  • High measurement range: Measures insulation resistance up to 500 GΩ for comprehensive testing.
  • Fast and stable measurements: Short circuit current of up to 5 mA for quick and reliable results.
  • Automatic calculations: Calculates Polarization Index (PI) and Dielectric Absorption Ratio (DAR) for easy analysis.
  • Durable and portable: Rugged design for use in demanding environments.
Category:

Description

The Fluke 1535/1537 Insulation Resistance Tester and Megohmmeter is a high-voltage insulation tester designed for validating general circuits, such as switchgear, motors, and cables. It offers a range of features and capabilities for efficient and accurate insulation resistance testing:

Key Features:

  • User-selectable test voltages: Choose from 250 V, 500 V, 1000 V, and 2500 V to suit various testing needs.
  • High measurement range: Measures insulation resistance up to 500 GΩ for comprehensive testing.
  • Fast and stable measurements: Short circuit current of up to 5 mA for quick and reliable results.
  • Automatic calculations: Calculates Polarization Index (PI) and Dielectric Absorption Ratio (DAR) for easy analysis.
  • Durable and portable: Rugged design for use in demanding environments.

Additional Features of the Fluke 1537:

  • ACV/DCV/resistance measurement: For added versatility.
  • Adjustable test voltage: From 250 V to 2500 V in 100 V increments.
  • Dielectric discharge (DD): For safe discharge of stored energy.
  • Ramp mode: Linearly increases test voltage for controlled testing.
  • User-definable tags, timed tests, and measurement results storage: For customized testing and data management.
  • Breakdown voltage indicator: Alerts user to potential insulation failure.
  • Mini USB interface: For data transfer to PC.

Benefits of Using the Fluke 1535/1537:

  • Improved safety: Identifies potential insulation failures to prevent electrical hazards.
  • Increased efficiency: User-friendly interface and automated features streamline testing.
  • Enhanced reliability: Regular insulation testing maintains the integrity of electrical systems.

Overall, the Fluke 1535/1537 is a powerful and versatile tool for ensuring the safety and reliability of electrical systems. It is suitable for a wide range of applications, including industrial, commercial, and residential settings.

Additional information

Brand

Fluke

Specifications: Fluke 1535 and 1537 Insulation Resistance Tester and Megohmmeters

General Specifications
Display 73.5 mm x 104 mm
Battery 8 AA alkaline cells, IEC LR6
Dimensions (H x W x L) 184 mm x 211 mm x 93 mm
Weight 1.3 kg
Temperature
Operating temperature -10 °C to +50 °C
Storage temperature -20 °C to +60 °C
Operating humidity Non-condensing (<10 °C)
≤80 % RH (10 °C to 30 °C)
≤50 % RH (30 °C to 50 °C)
Altitude
Operating altitude 2000 m
Storage altitude 12000 m
Overvoltage category CAT IV 600 V
Safety
General IEC 61010-1, Pollution Degree 2
IEC 61557-1
Measurement IEC 61010-2-030: CAT IV 600 V
IEC 61010-2-034: 2500 V dc
Insulation resistance measurement IEC 61557-1, IEC 61557-2
IP Rating IEC 60529 IP40
Electromagnetic Compatibility (EMC)
International IEC 61326-1: Electromagnetic environment for portable equipments
IEC 61326-2-2 CISPR 11: Group 1, Class A

 

Electrical Specifications
The meter’s accuracy is specified for one year after calibration at operating temperatures of 10°C to 30°C. For operating temperatures outside the range (-10°C to +10°C and +30°C to +50°C), add ± 0.25% per °C, except on the 20% bands, add ± 1% per °C.
Insulation resistance testing
Test voltage Range Resolution Accuracy
250 V <200 kΩ Unspecified Unspecified
200 kΩ to 500 kΩ 1 kΩ 5 %
0.50 MΩ to 5.00 MΩ .01 MΩ 5 %
5.0 MΩ to 50.0 MΩ 0.1 MΩ 5 %
50 MΩ to 500 MΩ 1 MΩ 5 %
0.50 GΩ to 5.00 GΩ 0.01 GΩ 5 %
5.0 GΩ to 50.0 GΩ 0.1 GΩ 20 %
>50 GΩ Unspecified Unspecified
500 V <200 kΩ Unspecified Unspecified
200 kΩ to 500 kΩ 1 kΩ 5 %
0.50 MΩ to 5.00 MΩ .01 MΩ 5 %
5.0 MΩ to 50.0 MΩ 0.1 MΩ 5 %
50 MΩ to 500 MΩ 1 MΩ 5 %
0.50 GΩ to 5.00 GΩ 0.01 GΩ 5 %
5.0 GΩ to 10.0 GΩ 0.1 GΩ 5 %
10.0 GΩ to 50.0 GΩ 0.5 GΩ 20 %
50 GΩ to 100 GΩ 5 GΩ 20 %
>100 GΩ Unspecified Unspecified
1000 V <200 kΩ Unspecified Unspecified
200 kΩ to 500 kΩ 1 kΩ 5 %
0.50 MΩ to 5.00 MΩ .01 MΩ 5 %
5.0 MΩ to 50.0 MΩ 0.1 MΩ 5 %
50 MΩ to 500 MΩ 1 MΩ 5 %
0.50 GΩ to 5.00 GΩ 0.01 GΩ 5 %
5.0 GΩ to 20.0 GΩ 0.1 GΩ 5 %
20.0 GΩ to 50.0 GΩ 0.5 GΩ 20 %
50 GΩ to 200 GΩ 5 GΩ 20 %
>200 GΩ Unspecified Unspecified
2500 V <200 kΩ Unspecified Unspecified
200 kΩ to 500 kΩ 1 kΩ 5 %
0.50 MΩ to 5.00 MΩ 0.01 MΩ 5 %
5.0 MΩ to 50.0 MΩ 0.1 MΩ 5 %
50 MΩ to 500 MΩ 1 MΩ 5 %
0.50 GΩ to 5.00 GΩ 0.01 GΩ 5 %
5.0 GΩ to 50.0 GΩ 0.1 GΩ 5 %
50 GΩ to 500 GΩ 5 GΩ 20 %
>500 GΩ Unspecified Unspecified

Insulation test voltage accuracy: -0 %, +10 % @ 1 mA load current Charging rate for capacitive load: 5 s/μF Discharging rate for capacitive load: 1.5 s/μF

  Range Accuracy
Leakage current measurement 1 nA to 2 mA ±(20 % + 2 nA)
Capacitance measurement 0.01 μF to 2.00 μF ±(15 % rdg + 0.03 μF)
Test voltage for insulation resistance 250 V to 2500 V ±(3 % + 3 V)

 

Warning for energized circuit
Warning range >30 V

 

Timer (F1537 only)
Range 0 to 99 min
Resolution Setting: 1 min Alert: 1 s

 

Short circuit current
F1535 >2 mA
F1537 >5 mA

 

ACV/DCV/resistance measurement (1537 only)
Function Range Resolution Accuracy
±(% rdg + dgt)
VAC 0 V to 600.0 V 0.1 V ±(2 % +10)
(45 Hz to 500 Hz)
VDC 0 V to 600.0 V 0.1 V ±(2 % +10)
Resistance 0 Ω to 600.0 Ω 0.1 Ω ±(2 % +10)
600 Ω to 6000 Ω 1 Ω