Gossen METRACLIP 88 Clamp Multimeter
- Clamp opening: 60 mm
- Current:
- AC 99,99 / 999,9 / 2000 A rms bei 10 Hz – 1 kHz
- DC ±99,99 / ±999,9 / ±3000 A dc
- AC+DC 99,99 / 999,9 / 2000 A rms
- 99,99 / 999,9 / 3000 A peak
- Inrush current: 20 ..2000 A rms / 3000 A peak
- Voltage:
- AC 99,99 / 999,9 V rms bei 10 Hz – 3 kHz
- DC ±99,99 / ±999,9 V dc
- AC+DC 99,99 / 999,9 V rms
- 99,99 / 999,9 / 1400 V peak
- Frequency:
- f (Uac) 5,0 Hz ..19,99 kHz
- f (Iac) 5,0 Hz ..999,9 Hz
- Power:
- Active power: 9999 W / 99,99 / 999,9 / 3000 kW
- Apparent power: 9999 VA / 99,99 / 999,9 / 3000 kVA
- Reactive power: 9999 var / 99,99 / 999,9 / 3000 kvar
- PF -1,00 ..+1,00
- DPF 0,00 ..1,00
- Distortion:
- Ripple 0,1 ..1000 %
- CF 1,00 ..10,00
- THDr / THDf 0,0 ..100 % / 0,0 ..1000 %
- Description
- Additional information
- Specifications
Description
The METRACLIP 88 is a high-performance clamp meter from Gossen Metrawatt specifically designed for measuring high currents and power in industrial environments.
Key Features:
- Electrical safety per IEC 61010
- TRMS measurement
- Current measurement (AC and DC)
- Voltage measurement (AC and DC)
- Power measurement (W, VA, var and PF)
- THD measurement
- Starting and overcurrent measurement (true inrush)
- Frequency measurement
- Automatic measuring range selection
- Relative and differential measurements
- Display value storage (Data Hold)
- Data logging (min., max., peak)
- Continuity test, acoustic signal
- Resistance measurement
- Diode test
- Phase sequence display
- Phase sequence
- LCD / digits backlit in blue10,000
- Auto power-off
- Test report incl.
- High Current Measurement: Measures high AC/DC currents with a wide measurement range.
- Large Clamp Opening: Accommodates large conductors, making it suitable for measuring current in thick cables or busbars.
- Power Measurements: Measures active, apparent, and reactive power.
- True RMS Measurement: Ensures accurate readings even with non-sinusoidal waveforms.
- Contactless Current Measurement: Enables safe and efficient current measurement without touching the conductor.
- Rugged Construction: Built to withstand the demands of industrial environments.
Applications:
- Industrial Maintenance: Monitoring current flow in motors, transformers, and other high-power industrial equipment.
- Power Distribution: Measuring current and power in power lines and substations.
- Electrical Installation: Troubleshooting high-current circuits and verifying proper installation.
In essence, the METRACLIP 88 is a robust and reliable tool for professionals who need to measure high currents and power accurately and safely in demanding industrial environments.
Additional information
Brand | Gossen Metrawatt |
---|
Characteristic Values
METRACLIP 86 | METRACLIP 85 | METRACLIP 88 | METRACLIP 87 | |
Item number | M312K | M312J | M312M | M312L |
Reactive power AC | 1Watt – 600000Watt | 1Watt – 2000000Watt | 1Watt – 1000000Watt | |
Continuity test | x | x | x | x |
THDr | 0.001 – 1 | 0.0001 – 1 | 0.0001 – 1 | |
Reactive power AC+DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Frequency measuring range for AC currents | 1Hertz – 3000Hertz | 0.1Hertz – 3000Hertz | 0.1Hertz – 1000Hertz | 0.1Hertz – 2000Hertz |
Frequency measuring range for AC voltages | 1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz | 0.1Hertz – 20000Hertz |
Max. voltage measuring circuit category | 600Volt | 600Volt | 1000Volt | 1000Volt |
Diode test | x | x | x | |
Voltage measuring range AC | 0.1Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt |
Phase sequence determination | x | x | ||
Apparent power AC | 1Voltampere – 600000Voltampere | 1Voltampere – 2000000Voltampere | 1Voltampere – 1000000Voltampere | |
THDf | 0.001 – 10 | 0.0001 – 10 | 0.0001 – 10 | |
AC measuring method | TRMS | TRMS | TRMS | TRMS |
Intrinsic uncertainty of the measured value in % | 0.4Percentage | 0.4Percentage | 1Percentage | 1Percentage |
Active power DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Power factor PF | 0.01 – 1 | 0.01 – 1 | 0.01 – 1 | |
Resistance measurement range | 0.1Ohm – 60000Ohm | 0.1Ohm – 60000Ohm | 0.1Ohm – 1000Ohm | 0.1Ohm – 100000Ohm |
Measured value memory | HOLD MAX MIN PEAK |
HOLD MIN MAX |
HOLD MAX MIN PEAK |
HOLD MAX MIN PEAK |
Active power AC+DC | 1Watt – 900000Watt | 1Watt – 3000000Watt | 1Watt – 1500000Watt | |
Active power AC | 1Watt – 600000Watt | 1Watt – 2000000Watt | 1Watt – 1000000Watt | |
Apparent power AC+DC | 1Voltampere – 900000Voltampere | 1Voltampere – 3000000Voltampere | 1Voltampere – 1500000Voltampere | |
Voltage measuring range DC | 0.1Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt | 0.01Volt – 1000Volt |
Indication | Digital | Digital | Digital | Digital |
Analogue bar graph display | ||||
Measuring range selection | Automatic | Automatic | Automatic | Automatic |
Current measuring range, DC | 0.01 – 900 | 0.01 – 900 | 1 – 3000 | 0.01 – 1500 |
Current measuring range, AC | 1 – 600 | 0.01 – 600 | 1 – 2000 | 0.01 – 1500 |
Type of current | AC/DC | AC/DC | AC/DC | AC/DC |
True RMS measurement | x | x | x | x |
Voltage measurement, AC | x | x | x | x |
Voltage measurement, DC | x | x | x | x |
Resistance measuring range | x | x | x | x |
Power measuring | x | x | x | |
Leakage current measuring | x | x | x | x |
Harmonics measurement | x | x | x | |
Measurement in cables with for- and back conductor | x | x | x | x |
Jaw opening | 34 | 34 | 60 | 48 |
Version as adapter to connect to multi meter | ||||
Interface | x | |||
Measuring circuit category | CAT IV | CAT IV | CAT IV | CAT IV |
Adapter function AC | ||||
Frequency range alternating current | 0Hertz – 1000Hertz | 0Hertz – 2000Hertz | ||
Temperature measuring range | ||||
Adapter function DC | ||||
Frequency range volt AC | 0Hertz – 3000Hertz | 0Hertz – 3000Hertz | ||
Displacement factor DPF | 0.01 – 1 | |||
Ripple | 0.1 – 10 | |||
Crest factor CF | 1 – 10 | |||
Voltage measuring range AC+DC | 0.01Volt – 1000Volt | |||
Current measurement range AC+DC | 0.01Ampere – 1500Ampere |