Gossen MAVOWATT 210 Data Logger for Power Quality
- Power/energy logger and PQ disturbance/event detector
- 3 voltage channels – direct measurements up to 600 V RMS, CAT III
- 4 current channels – 0.333 V RMS current inputs, compatible with various optional accessories (see accessories lists) and all 0.333 V RMS current transformers which comply with industry standards
- Measurement types: V, I, W (P), VA (S), VAR (Q), PF, demand measurement for various quantities, energy … and much more
- Detection and recording of trends for RMS voltage dips/sags, swells, current changes in accordance with IEC 61000-4-30 in 1/2 cycle methods
- Vthd and Ithd measurements using methods of IEEE 519-2014 / IEC 61000-4-7
- Web browser interface for real-time measurements, setup and data transfer
- Free Dran-View XP software for analysis and reporting available for download at “MyGMC”
- 7 hours battery life for long-term measurements
- Automatic wiring test: LEDs indicate wiring errors
- Ethernet, USB communication
- Modbus, Bacnet
- IP50 (vertical position)
- Description
- Additional information
- Specifications
Description
The MAVOWATT 210 is a three-phase power and energy logger designed for monitoring and analyzing electrical power systems.
Key Features:
- Accurate Measurements: Precisely measures key electrical parameters like voltage, current, power, energy, frequency, and power factor.
- Data Logging: Records measurement data over extended periods, enabling trend analysis and long-term monitoring of power consumption.
- Energy Analysis: Provides detailed analysis of energy consumption patterns, helping to identify areas for improvement and potential cost savings.
- Power Quality Monitoring: Detects and records common power quality issues such as voltage sags, swells, and harmonics.
- User-Friendly Interface: Features a user-friendly interface for easy setup, operation, and data retrieval.
- Compact and Portable: Designed for easy installation and portability.
Benefits:
- Energy Cost Savings: Identifies areas for energy efficiency improvement, leading to reduced energy costs.
- Improved System Reliability: Detects and diagnoses potential power quality issues that could lead to equipment failures.
- Enhanced System Monitoring: Provides valuable insights into the performance of electrical systems.
- Data-Driven Decisions: Enables data-driven decisions regarding energy management and system optimization.
Applications:
The MAVOWATT 210 is suitable for a wide range of applications, including:
- Industrial facilities: Monitoring energy consumption in factories, plants, and other industrial sites.
- Commercial buildings: Analyzing energy usage in offices, retail stores, and other commercial properties.
- Residential applications: Monitoring energy consumption in homes and apartments.
- Utility companies: Monitoring power quality and energy consumption on distribution grids.
The MAVOWATT 210 is a valuable tool for anyone looking to monitor and analyze energy consumption and power quality. Its accurate measurements, data logging capabilities, and user-friendly interface make it a reliable and effective solution for a wide range of applications.
Additional information
Brand | Gossen Metrawatt |
---|
Characteristic Values
MAVOWATT 270-400 | MAVOWATT 240 | MAVOWATT 270 | MAVOWATT 230 | MAVOWATT 210 | |
Item number | M820K | M820B | M820C | M820A | M840B |
Product details page | Details | Details | Details | Details | Details |
Indication | Graphic | Graphic | Graphic | Graphic | None |
Number of voltage input channels | 4 | 4 | 4 | 4 | 4 |
Number of current input channels | 4 | 4 | 4 | 4 | 4 |
Current measurement | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter |
Harmonics measurement | x | x | x | x | |
Power factor | x | x | x | x | x |
Effective power | x | x | x | x | x |
Reactive power | x | x | x | x | x |
Apparent power | x | x | x | x | x |
Step angle (cos phi) | x | x | x | x | x |
Power/work | x | x | x | x | x |
Interface | x | x | x | x | x |
Measured value memory | x | x | x | x | x |
Current supply | Battery (rechargeable)/mains | Battery (rechargeable)/mains | Battery (rechargeable)/mains | Battery (rechargeable)/mains | Accumulator/mains |
Voltage measuring range/AC direct | 0 – 1000 | 0 – 1000 | 0 – 1000 | 0 – 1000 | 90V – 600V |
Communication | Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Bluetooth VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet USB |
Input | Differential, voltage channels, 0 to 1000�V�AC/DC | Differential, voltage channels, 0 to 1000�V�AC/DC | Differential, voltage channels, 0 to 1000�V�AC/DC | Differential, voltage channels, 0 to 1000�V�AC/DC | |
Measurement | 1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 32/40µs (60/50Hz) Transients as of 1µs Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 400 Hz monitoring |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 32/40µs (60/50Hz) Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 32/40µs (60/50Hz) Transients as of 1µs Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 32/40µs (60/50Hz) Power demand and energy consumption Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
|
Answer modules | Motor status Voltage dip direction Switching of compensation capacitors |
Motor status Voltage dip direction Switching of compensation capacitors |
Motor status Voltage dip direction Switching of compensation capacitors |
Motor status | |
Set-ups | Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Monitoring operating modes Setup wizard Max. pre/post-trigger periods |
|
Max. pre-/post-trigger periods | 100000 | 100000 | 100000 | 100 | |
Frequency measuring range | 16?, 50 to 60�Hz | ||||
Top arbour measurement |