Gossen MAVOWATT 210 Data Logger for Power Quality

  • Power/energy logger and PQ disturbance/event detector
  • 3 voltage channels – direct measurements up to 600 V RMS, CAT III
  • 4 current channels – 0.333 V RMS current inputs, compatible with various optional accessories (see accessories lists) and all 0.333 V RMS current transformers which comply with industry standards
  • Measurement types: V, I, W (P), VA (S), VAR (Q), PF, demand measurement for various quantities, energy … and much more
  • Detection and recording of trends for RMS voltage dips/sags, swells, current changes in accordance with IEC 61000-4-30 in 1/2 cycle methods
  • Vthd and Ithd measurements using methods of IEEE 519-2014 / IEC 61000-4-7
  • Web browser interface for real-time measurements, setup and data transfer
  • Free Dran-View XP software for analysis and reporting available for download at “MyGMC”
  • 7 hours battery life for long-term measurements
  • Automatic wiring test: LEDs indicate wiring errors
  • Ethernet, USB communication
  • Modbus, Bacnet
  • IP50 (vertical position)

Description

The MAVOWATT 210 is a three-phase power and energy logger designed for monitoring and analyzing electrical power systems.

Key Features:

  • Accurate Measurements: Precisely measures key electrical parameters like voltage, current, power, energy, frequency, and power factor.
  • Data Logging: Records measurement data over extended periods, enabling trend analysis and long-term monitoring of power consumption.
  • Energy Analysis: Provides detailed analysis of energy consumption patterns, helping to identify areas for improvement and potential cost savings.
  • Power Quality Monitoring: Detects and records common power quality issues such as voltage sags, swells, and harmonics.
  • User-Friendly Interface: Features a user-friendly interface for easy setup, operation, and data retrieval.
  • Compact and Portable: Designed for easy installation and portability.

Benefits:

  • Energy Cost Savings: Identifies areas for energy efficiency improvement, leading to reduced energy costs.
  • Improved System Reliability: Detects and diagnoses potential power quality issues that could lead to equipment failures.
  • Enhanced System Monitoring: Provides valuable insights into the performance of electrical systems.
  • Data-Driven Decisions: Enables data-driven decisions regarding energy management and system optimization.

Applications:

The MAVOWATT 210 is suitable for a wide range of applications, including:

  • Industrial facilities: Monitoring energy consumption in factories, plants, and other industrial sites.
  • Commercial buildings: Analyzing energy usage in offices, retail stores, and other commercial properties.
  • Residential applications: Monitoring energy consumption in homes and apartments.
  • Utility companies: Monitoring power quality and energy consumption on distribution grids.

The MAVOWATT 210 is a valuable tool for anyone looking to monitor and analyze energy consumption and power quality. Its accurate measurements, data logging capabilities, and user-friendly interface make it a reliable and effective solution for a wide range of applications.

Additional information

Brand

Gossen Metrawatt

Characteristic Values

MAVOWATT 270-400 MAVOWATT 240 MAVOWATT 270 MAVOWATT 230 MAVOWATT 210
Item number M820K M820B M820C M820A M840B
Product details page Details Details Details Details Details
Indication Graphic Graphic Graphic Graphic None
Number of voltage input channels 4 4 4 4 4
Number of current input channels 4 4 4 4 4
Current measurement With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter
Harmonics measurement x x x x
Power factor x x x x x
Effective power x x x x x
Reactive power x x x x x
Apparent power x x x x x
Step angle (cos phi) x x x x x
Power/work x x x x x
Interface x x x x x
Measured value memory x x x x x
Current supply Battery (rechargeable)/mains Battery (rechargeable)/mains Battery (rechargeable)/mains Battery (rechargeable)/mains Accumulator/mains
Voltage measuring range/AC direct 0 – 1000 0 – 1000 0 – 1000 0 – 1000 90V – 600V
Communication Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Bluetooth
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
USB
Input Differential, voltage channels, 0 to 1000�V�AC/DC Differential, voltage channels, 0 to 1000�V�AC/DC Differential, voltage channels, 0 to 1000�V�AC/DC Differential, voltage channels, 0 to 1000�V�AC/DC
Measurement 1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 32/40µs (60/50Hz)
Transients as of 1µs
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
400 Hz monitoring
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 32/40µs (60/50Hz)
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 32/40µs (60/50Hz)
Transients as of 1µs
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 32/40µs (60/50Hz)
Power demand and energy consumption
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
Answer modules Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Set-ups Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Monitoring operating modes
Setup wizard
Max. pre/post-trigger periods
Max. pre-/post-trigger periods 100000 100000 100000 100
Frequency measuring range 16?, 50 to 60�Hz
Top arbour measurement

 